Solution and Answer Guide: John Siegenthaler, Modern Hydronic Heating and Cooling 2023, ISBN: 9781337904919; Chapter 1: Fundemental Concepts

Solution and Answer Guide Solution and Answer Guide: John Siegenthaler, Modern Hydronic Heating and Cooling 2023, ISBN: 9781337904919; Chapter 1: Fundamental Concepts TABLE OF CONTENTS End of Section Exercise Solutions .............................................................................. 1

END OF SECTION EXERCISE SOLUTIONS 1. Why does ducting in forced-air heating systems have to be so much larger than the tubing in a hydronic heating system of equal heating capacity? Solution Due to higher heat capacity compared to air, the volume of water that must be moved through a building to deliver a certain amount of heat is only about 0.03% that of air. Since flow rate of water to deliver the same amount of heat is lower, the distribution system size can be reduced. 2. Why is it better to surround a person with warm surfaces as opposed to just warm air? Solution People’s bodies lose thermal energy via radiant heat transfer from their skin surfaces to nearby colder surfaces. For this reason, most people will not be comfortable in a room containing several cool surfaces such as large windows or cold floors, even if the room’s temperature is 70 F. 3. What type of heat transfer creates the wind chill effect we experience during winter? Solution Forced Convection 4. A certain block of material conducts heat at a rate of 100 Btu/h. One side is maintained at 80 F and the other at 70 F. Describe what happens to the rate of heat transfer when the: a. The 80 F side is raised to 130 F b. The thickness of the block is doubled c. The 80 F side is raised to 130 F, and the thickness is cut in half

© 2023 Cengage. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.

1


Solution and Answer Guide: John Siegenthaler, Modern Hydronic Heating and Cooling 2023, ISBN: 9781337904919; Chapter 1: Fundemental Concepts

Solution a. Assuming that the opposite side of the block is maintained at a temperature of 70 F, the rate of heat transfer would increase. b. If the material thickness is increased (doubling in this case), then the rate of heat transfer would decrease. c. Assuming that the opposite side of the block is maintained at 70 F, the rate of heat transfer would increase.

5. At approximately what temperature does a surface that is cooling from a high temperature stop emitting visible radiation? Solution As the surface of a material cools below about 970 F, the frequency of light the surface emits is no longer in the visible spectrum and, therefore not detectable by our eyes. 6. How does thermal radiation differ from visible light? In what ways are they similar? Solution Thermal radiation and visible light are both forms of electromagnetic energy. Thermal radiation and visible light differ only in their wavelengths, with the wavelength of thermal radiation being larger than that of visible light. 7. Describe thermal equilibrium within a hydronic system. Solution When a hydronic system is in thermal equilibrium, the rates of heat input to and heat release from the working fluid are equal, and the working fluid temperatures at all locations in the system are stable (no change with time). 8. What is the function of a feed water valve in a hydronic system? Solution The feed water value is used to reduce pressure and maintain a constant minimum pressure in the system. 9. What is the difference between an open-loop system and a closed-loop system? Solution © 2023 Cengage. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.

2


Solution and Answer Guide: John Siegenthaler, Modern Hydronic Heating and Cooling 2023, ISBN: 9781337904919; Chapter 1: Fundemental Concepts

In a closed-loop system, the circuit is sealed off from the atmosphere at all locations. An open-loop system is open to the atmosphere at one or more points. 10. Are there any closed-loop hydronic heating systems on which a pressure-relief valve is not required? Why? Solution No, all closed-loop hydronic systems must be protected by a pressure-relief valve.

11. List two types of hydronic heat emitters other than finned-tube baseboard convectors. Solution Fan-Coil or Air Handlers Radiant Panel 12. What is the function of a flow-check valve in a single-loop system? Solution In a single-loop system, the purpose of the flow-check valve is to prevent hot water in the boiler from slowly circulating through the distribution system when the circulator is off. 13. What is a “brine”? In what type of hydronic heating application would it be used? Solution The term “brine” is a generic word for a solution of water and antifreeze such as propylene glycol, ethylene glycol, or calcium chloride. It would be used in special applications such as hydronic snowmelting where a pure water working fluid could freeze. 14. Why is it necessary to have a backflow preventer in the make-up water line? Solution The backflow preventer stops any water that has entered the system from returning and possibly contaminating the potable water supply system. 15. What are the customary units for heat and heat transfer rate in North America? Solution The unit for heat (thermal energy) is the British thermal unit (Btu). The unit for heat transfer rate is British thermal units per hour (Btu). 16. What is a “zoned” hydronic system?

© 2023 Cengage. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.

3


Solution and Answer Guide: John Siegenthaler, Modern Hydronic Heating and Cooling 2023, ISBN: 9781337904919; Chapter 1: Fundemental Concepts

Solution A heating system that allows different sections of a building to be maintained at different temperatures and thus can be adapted to the comfort needs of several individuals.

17. What made water flow through early hydronic systems before circulators were used? Solution Early hydronic systems relied on the buoyancy of hot water to circulate water between the boiler and the heat emitters. Because of its lower density, hot water would rise upward from a boiler through supply pipes into heat emitters. After releasing heat, the now slightly heavier water flowed downward back to the boiler. 18. What causes air bubbles to form within an air separator? Solution The separator creates regions of reduced pressure as the water passes through. The lowered pressure causes the dissolved gasses in the water to form into bubbles. 19. How are the expansion tanks used in modern hydronic systems different from those used in older systems? Solution Most modern hydronic systems use diaphragm-type expansion tanks. Such tanks contain their captive air in a sealed chamber. Older hydronic systems often used expansion tanks without diaphragms. Tanks lacking diaphragms had to be mounted higher than the heat source and were considerably larger than modern, diaphragm-type tanks. 20. What are some common ways small amounts of water leak out of a closed-loop hydronic system? Solution Most closed-loop hydronic systems experience minor water loss over time due to evaporation from valve packing, pump seals, air vents, and other components.

© 2023 Cengage. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.

4


Solution and Answer Guide: John Siegenthaler, Modern Hydronic Heating and Cooling 2023, ISBN: 9781337904919; Chapter 1: Fundemental Concepts

Solution and Answer Guide Solution and Answer Guide: John Siegenthaler, Modern Hydronic Heating and Cooling 2023, ISBN: 9781337904919; Chapter 2: Space Heating and Domestic Water Heating Loads TABLE OF CONTENTS End of Section Exercise Solutions .............................................................................. 7 © 2023 Cengage. All Rights Reserved. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.

5


Turn static files into dynamic content formats.

Create a flipbook
Solution Manual for Modern Hydronic Heating For Residential and Light Commercial Buildings, 4th Edit by AnswerDone - Issuu