intro

Fitzpatrick+partners was invited in April 2008 by St Hilliers to take part in a Design Excellence Competition for the development of their site in Argyle Street Parramatta. The concept presented is our interpretation of the brief, and in particular: “...to produce a feasible and commercially viable design that is attractive to government and commercial tenants, that responds to the site’s context and constraints and opportunities of the site itself, maximises opportunities for ecologically sustainable design, achieves design excellence and improves the urban domain of Parramatta City.�


theteam 120768743 Dinorah Martinez Schulte 1218916 Edward white 1037025 Jash Rajeswaran

- Retail and Gaming Lobby - Bar and Rooftop - A typical office floor


index 03 05 08 15 16 35 58 76 67 100 102

Introduction: Information about building Contact details for group members Architectural Analysis - Inmediate Context: Public Realm - Parts of the Building: Actual Program - Transportation and conections - Lighting and Solar Studio

Matrix New Proposal (Complete Building) - Parts of the Building: New Program - Ecotech Studio -Dialux Studio

Retail and lobby - Lighting Appraisal - Acoustic Appraisal - Thermal Appraisal

A typical office floor - Lighting Appraisal - Acoustic Appraisal - Thermal Appraisal

Bar and Gaming - Lighting Appraisal - Acoustic Appraisal - Thermal Appraisal

Comfort Analysis Reflections and conclutions Bibliography


architectural analysis


FI TZ

Circulation AR

W GY

IL LI AM ST RE

LE

ET

ST RE ET

Location

Site

Transportation

Bus Station

Inmediate Context

SYDNEY WATER

PARRAMATTA PRINCIPAL BUS STATION

OLD PARRAMATTA BUS STATION

RAFFLES COLLAGE OF DESIGN AND COMMERCE

CIRCA CEFE

MANTRA PARRAMATA

COMMERCIAL HOTEL

pubicrealm


BUILDINGSTUDIO 100 m.

HEIGHT AND SHAPE

80 m.

The building has a very good height to have very good views and the orientation is always good because the principal facade is orientate to the north but, it has a lot of daylight the most of the day and the shape is very basic, rectangular plan. It is not proposing and shadow system with the same structure, it is very plan and basic.

COMPOSITION OFFICES COLUMNS

CIRCULATIONS HOTEL AND LOBBY PRINCIPAL ACCESS GROUND LEVEL

PRIVACITY


VIEWSECTIONS SYDNEY CBD

PARRAMATTA BUS STATION N

THE BUILDING AND THE CONTEXT

ORIENTATION

The building is surrounded by not very tall buildings with 4 or 5 levels therefore do not provide any exterior facade shadows anywhere.

The orientation of the building is NORTH EAST, so we have the cold facade infront but there are not any buulding protecting and it transforms to the hotest.

Arcoustics and visuals floats for pedestrians buses and trains underneath the office levels

NE

The view corridor for the historic statiorn building is reinstated.

VIEWS

The building has incredible views in offices and on the rooftop to the Sydney CBD and historic Parramatta station which will create great importance to these two urban landmarks and makes the top capital gains has more importance and the part down.

Outlook and views are maximised.


DAYLIGHTSTUDIO 7:00 AM TO 6:00PM

S

W

S

6:11 PM

W 5:55 PM

9:00 AM

7:00 AM

5:55 AM 5:35 AM

16 March

E

N

29 September

E

7:00 AM

N

9:00 AM

All the buildings are not creating any shadow to the building, the sun is directly to the principal facade of the offices, so it is very inconfortable and we will need to use curtains or lattice system to protect offices in the morning because it is the time of begin to work.

Its happening the same effect but now the sun is more direct to the principal facade so we have same problem, it will be a very hot place inside offices and the hotel level too. 5:00 PM

12:00 PM

S

S

W

W

6:11 PM

5:55 PM

5:55 AM

16 March

5:35 AM

E

29 September

E

12:00 PM

We have a very hot place, very directly light in both sizes of the building that it is mean that it is a veru hot place and actually has too much sun light so you dont need artificial light for this hour also in the ground floor. In spite of that, we have a very hot offices to be protect. THE WORST HOUR!

N

6:00 PM

All the buildings are making shadows to the principal facade but its not enought because we now have very hot place in the other site, and no too much sense because there is not too much people because offices are closed yet. Not too much sun light for this our.

N


DAYLIGHTSTUDIO December to Junuary

12:03 PM

12:03 PM

7:03 PM

S

W

S

W 6:13 PM

20 December

4:41 AM

E

5:55 AM

N

15 March

E

DECEMBER

N

MARCH 12:03 PM

S

W

S

6:16 PM

W

12:03 PM 5:00 PM

26 October

E

7:00 AM

10 July

JULY

N

5:01 AM

E

OCTOBER

N


MATRIX The matrix provided allows you to document your function and program analysis and emerging environmental concept. While you should detail these for each space, you should also list any overarching environmental goals for the building as a WHOLE. Nature and character of Functional Other Design Lighting Daylighting Thermal Thermal control Background space (design Space concept) requirements Criteria requirements potential requirements options Sound

Ground Floor Retail with association to the street and void

Each Outlet needs its own pressence. Audio, Visual and sensory comfort.

Office Floor (with some open plan and break out areas) Quiet and comfortable adjoining the workspace atrium

Bar and Gaming Loud and exciting Lobby

needs uniform glare free lighting at task areas, code 600 lux. Design spaces of Easily inspiration with Accessible from great views and the station with Reduce maximum visual excessive glare good enviroment daylighting frontage from the sun internal space desirable

Noise from retail and Set layout with Bar(all day) flexible working must be spaces mitigated

Long Reverbations No sound and appropriate leakage to the airflow office

45-50 dBA (The focus here is to block out the exterior Zoned airconditioning traffic noise Provision of & risers to flush and engage in the Fresh and out hot air & microclimate of conditioned air. smells. the internal Comfortable to Operable be in 19-25C. windows. environment.)

comfortable to work in need to manage typically 19needs uniform overheating in 25C if user glare free lighting summer, control; 20-24 Natural at task areas, code 320 lux. ventilation daylighting very if no user Design spaces of desirable but in control, alone will not humidity not a work…possibly inspiration with morning great views exaggerated major concern mixed mode

needs uniform glare free lighting at task areas, code 240 lux. Design spaces of inspiration with create a good daylighting space desirable

Cross ventilation

40dBA in quiter office areas to 45dBA in break out areas where conversation is needed

45 - 50dBA (a focus on internal sounds Operable portions of the is needed to window above create this stimulating the fixed portion environment)

Intruding Sound Reverb-­‐eration Exterior traffic noise should not be a focus here. Managed through the door system and a partitioned entrance.

Ensure that Voices (of colleagues) are not a focus of attention

Speech Intelligibility

Good at 2m. Intelligibility is High - 1 to 1.3 not as much of (More reflective a focus as it is surfaces, Music a fast moving retail and in retail will circulatory sound more rich) environment.

Low – 0.4 to 0.6 allowing for a comfortable working environment

Medium - 0.7 to 1.0 (abosorabtive surfaces for Ensure that kitchen and bar patrons, more equipment are of a focus on not a focus of speech than in attention. retail area.

Good at 3m, allow for a conversation to be made from once desk to another.

Good at 1m. A loud environment to allow for multple conversations at any given time.

Implications for design Ease of access through the site; also a great thoroughfare for wind and daylight. We would like a bit of sound travelleing through the site so glass and tiles will reflect the sound well. Need to manage High internal loads, heat gains from façade while admitting daylight. Noise from meeting rooms and breakout area needs to be considered. The provision of fresh air. Important that sound does not leak into the offices from this space. Daylight and Night light will play a theatric feature in this design. High ceiling will allow high cross ventilation to reduce the humidity in the space.


NEW PROPOSAL


BUILDINGSTUDIO COMPOSITION

CIRCULATIONS BAR AND GAMING

PROS 1. We improve the sound levels for each room to have its appropriate level of inner sound and not interfere or disturb others. 2. Improved the main facade of the offices to improve its internal temperature and make a more pleasant work space.

OFFICES

3. Create a lobby with more open and less closed to improve its lighting and temperature and avoid using artificial light in most of the day as it is in the restaurant downstairs and it is difficult for you to get natural light with a roof very it closed as formerly had. 4. Decided to retain the main structure because it is part of the building and work to support the building structurally. 5. Create the use of a double glass as double facade to improve the lighting and temperature.

LOBBY AND RETAIL

6. We play and create a new geometry into the building to create a shutter with the same structure in all of the offices. 7. moved the restaurant to the top as a very public place and create an open and well-lit space also improve sound levels this place.

PRINCIPAL ACCESS GROUND LEVEL

8. We decided to keep the lobby open walls and windows were removed and completely permeable to allow users access from both streets surrounding the building and creating a view of the historic bus station basement was left Parramatta

The agenda of the current building is made up by the lobby at the bottom, followed by the hotel on the top floor and a bar, open to circulate air and above have offices space is left. We decided to change the program of the building and move the bar located in the middle part and move it to the rooftop of the building, and we think that acoustic problems is better to have this space on the top and not interrupt levels sound between the lobby and offices with lower noise levels to be public places, and open the roof of the lobby to promote natural lighting and ventilation of the building. The offices moved the main facade to promote lighting and the temperature inside the space because as we saw in the last analysis the building is not surrounded by high-rise buildings therefore causes no shade and protects the building from sunlight, this is the reason why we put a double facade Northeast facade of the building and moved her way doing a slice to the right favoring creating shadows and lighting and regulating the temperature above. The rooftop bar is a pretty good tool and move this program to the top does a more open space and so the sound levels may be higher and not have to worry about the lighting and natural ventilation.


Thermal Analysis There are a few thermal strategies incorporated in this building. 1. Heating and cooling through the ceiling and floor voids. 2. Natural Ventilation across the short distance of the floor plate which also provides fresh air to be returned and cooled or heated. 3. If all the windows in the buildings are closed, this would still function as the system would take flowing air from the void between the Lobby and the Offices. - The Bar and Gaming area uses the stack effect through its double layer to let heat rise to the top. It is then released by automated openings in the Roof Facade when the temperature increases beyond 23degC or when the humidity is above 50%. Fresh and cool air is channeled from the window openings of the Bottom Floor. The Bar and Gaming Area is also fitted with the underfloor ad ceiling system but we expect it not to need except in the cases of unforgiving weather such as heavy rain, hail or extreme heat waves. - The Lobby and Retail Zone utilises the stack effect well to move cooler air through the space and heat out through the perforated ceiling. The changing levels of the ceiling encourages movement of air across its surface. The challenge with such an open space is heating it. For this reason, each space in the Retail area is smaller and has insulated walls & flooring combined with the flooring being raised above the floor slab. - The Offices relies much more on the heating and cooling system but has break-out spaces that are all naturally ventilated and system free. Offices: Warmer Weather - The windows can be opened and allow cooler air to flow through and the return system can be activated to remove unwanted heat. Cooler Weather - Inside the office the Insulation in the floor and walls should be sufficient especially with the appliance & body heat but if it isn’t the underfloor heating can be activated.

Open-Aired Operable Roof Facade

Internal Louvres

Summer Sun

Winter Sun

Breakout Spaces: Warm Weather - Blinds can be opened to let air and daylight pass through the external facade, the windows can then be opened to further the cooling process. Cooler Weather - External Blinds can be closed to stop wind permeating the 1st layer of protection and not adding to the cooling effect. Low ceiling will help retain body and appliance heat. Double layered insulation between floor slab and floor panels should keep the floor quite warm. Insulation has been added between the accoustic panels and the ceiling. Summer Sun

Winter Sun

Service Free Rooms Natural Cooling and Heating Systems

Solar panels - convert solar energy into electricity via the power cells and are stored in a battery to power overhead lights.

2700mm

By reducing the room height, it will be easier to heat the room, with body heat and appliances etc.it will make the room more “cosy” and reduce the psychological ‘coldness’ of it.

2500mm

Without any Systems; and given a moderate outside temperature, the interior of the room will be slightly cold because of the altitude and wind passing by the window.

Lighting Program The lighting program is designed as follows: In the lobby and retail ceiling is separated at some distance and has averturas to let natural light and avoid making this area a very dark place, contrary to convert it into a brightly lit place for that type of material designated and design of the roof. The roof is ailiminado for all the vertices of a line of LED lights is the material with more life and provides as much light as light standards require. The office has the same system, but let in light right through a dual wrapped facade with a double glass system provided that all windows that open with respect to the inclination of the sun and allow partial step natural light without annoying space. Finally, the bar has a semi abrierto ceiling as he let all the natural light in the day and makes a very refreshing and bright atmosphere at night alone a fresh space is left and has also a system of ilumiacion LED This allows the entire roof lights and artificial light is distributed by a warm environment for users.

Summer Sun

Winter Sun

Service Free Rooms Natural Cooling and Heating Systems

Solar panels - convert solar energy into electricity via the power cells and are stored in a battery to power overhead lights.

45dBA Lower side - fixed double glazed glass

wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwww wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwww

- Underfloor cooling is implemented throughout the whole building design. The Chiller cools the air and pumps it under the raised floor. The raised floor also acts as a thermal barrier between the exposed concrete slab and the floorboards. Insulation between the floorboards and the concrete also helps stop the thermal bridging. - Warm air is returned through the ceiling void and is sent back down to the chiller to be re-chilled and circulated. In Winter; the air is boiled for underfloor heating and the cold air is sucked up through the vents.

Acoustic Program

- The solar panels help provide electricity to the lighting reducing the cost of lighting the building. Winter sunlight has also been maximised whilst reducing the amount of direct summer sun the floorplate is exposed to. - Fixed desks are set back to avoid glare but mixed use spaces or open plan space is malleable for those wanting more light.

Within this building there are various structural and material strategies in place in order for the various programs to perform acoustically. As the buildings context is a street front busy commercial area the facade of the building is under a lot of stress from external environmental noise. The increase of building height with the inclusion of the void allows for less noise transmission between the busy lower lobby and the performing office spaces above. With various acoustical detailing the reverberation rate and SPL of the various programs is lowered to meet their goals accordingly.

78 dBA - Bus leaving interchange SPL

Summer Sun

70 dBA medium traffic SPL on Facade at office level. 56dBA

Noise constraints include: • • • •

Winter Sun

background traffic level impact on the façade 70dBA at office level train leaving station 76dBA Bus leaving interchange 78 dBA at office level Truck in dock 73 dBA

73 dBA - Truck in dock SPL

SECTION 2 Y-Y’ 1:50

Chiller / Boiler


Floor Plates


Green Zones that are semi-eco


Windows on site


Load Bearing Walls


Complete Package


Types of Spaces: Acoustic Consultant Brief

Criteria

Windows

Glass

Wall partitions

Ceiling

Floor coverings

Extras

Office Floor

space of good speech intelligibility, block background noise Operable

Acoustic Glass with pottential to use patterned glass in office partitions

Quiet stud acoustical wall between office open plan and meeting room. Rw of 51.

Two layers of 13mm plasterboard RW - 32 additional ceiling tiles are needed to keep the ceiling as sound absorbant as possible

Meeting Rooms

Focus on high speech intelligibility and lower background sound

Non operable, to decrease dBA on internal

Acoustic Glass between meeting room and office open plan

Quiet stud acoustical wall between office open plan and meeting room. Rw of 51.

Concrete Slab direct Suspended Ceiling Rw of 64 - reduce sound Neoprene pads transmission between offices for sound Acoustic and Bar and vice versa isolation sealed Doors

Balance of Music and Speech intelligibility

Operable rooftop windows

Acoustic Glass Viridian VLam Hush™ is a laminate that uses a specially developed interlayer to Standard steel stud - Concrete Slab direct fixed dampen noise Insulated Rw of 50 Ceiling Rw of 59

Neoprene cork pads for sound isolation

High Speech intelligibility and low Background sound level

Closed internal with less windows to reduce glare to create a moreso internal environment

Acoustic Glass Viridian VLam Hush™ is a laminate that uses a specially developed interlayer to Standard steel stud - Suspended Ceiling for services Insulated Rw of 50 Rw of 64 dampen noise

Neoprene pads for sound Acoustic isolation sealed Doors

Fixed Double Glazing. With operable louvres to Reduce SPL of exterior traffic Standard steel stud within peak times. Insulated Rw of 50

Tiles

Bar

Gaming

Lobby

Retail

High Speech Intelligibility Lower range

Focus on Music - Higher range

Double Glazing between inidividual retail programs

Because of the double height ceiling and harder surfaces Ceiling Tiles for decreased reverberation

Quiet stud acoustical wall between office open Metal Pan PerforatedCeiling plan and meeting Tiles for decreased room. Rw of 51 reverberation

Slab with Carpet

Tiles. Underfloor Neoprene pads for sound isolation between individual retail program

Acoustic Wall Panels, Soft surfaces for sound absorbtion

Detailing Wall Partitions

Detailing Ceiling


ecotechSTUDIO


0900 Jun Perspective Daylight Analysis

0900 Dec Perspective Daylight Analysis


0900 Jun Perspective Daylight Analysis

0900 Dec Perspective Daylight Analysis


0900 Jun Perspective Daylight Analysis

0900 Dec Perspective Daylight Analysis


0900 Dec Persp

0900 Jun Persp

1500 Dec Persp

1500 Jun Persp


0900 Dec Sun View

0900 Jun Sun View

1500 Dec Sun View

1500 Jun Sun View


DIALUX ANALYSIS


graphicanalysis

FALSE COULOUR 3d RENDER

Room 1 / Luminaires (layout plan)

Scale 1 : 210 Luminaire Parts List No.

Pieces

1 2 3

12 20 23

Designation DIAL 17 1 HIT 35W DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ DIAL 5 Aufbaustrahler


diagramanalysis Room 1 / Summary

Height of Room: 5.000 m, Maintenance factor: 0.80 Surface

Project 1 / Luminaire parts list

E av [lx]

E min [lx]

E max [lx]

u0

Workplane

/

261

63

1465

0.243

Floor Ceilings (3)

27 80

248 615

66 108

1610 2992

0.265 /

Walls (6)

38

221

68

14016

/

Workplane: Height: 0.750 m Grid: 128 x 128 Points Boundary Zone: 0.500 m Illuminance Quotient (according to LG7): Walls / Working Plane:

- , Ceiling / Working Plane:

-.

Luminaire Parts List Pieces

1

12

2

20

3 4

23 50

Designation (Correction Factor)

(Luminaire) [lm]

(Lamps) [lm]

P [W]

2036

3400

42.0

4078

5500

78.0

3323 3256

5500 4650

78.0 56.0

509800

6658.0

DIAL 17 1 HIT 35W (1.000) DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ (1.000) DIAL 5 Aufbaustrahler (1.000) DIAL 9 Wave, 1 T16 54W, EVG (1.000) Total:

Specific connected load: 15.46 W/m

DIAL 17 1 HIT 35W Article No.: 17 Luminous flux (Luminaire): 2036 lm Luminous flux (Lamps): 3400 lm Luminaire Wattage: 42.0 W Luminaire classification according to DIN: E10 CIE flux code: 00 00 00 00 60 Fitting: 1 x HIT 35W (Correction Factor 1.000).

20 Pieces

DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ Article No.: 22 Luminous flux (Luminaire): 4078 lm Luminous flux (Lamps): 5500 lm Luminaire Wattage: 78.0 W Luminaire classification according to DIN: E13 CIE flux code: 00 00 12 00 74 Fitting: 1 x HIT -DE 70W (Correction Factor 1.000).

23 Pieces

DIAL 5 Aufbaustrahler Article No.: 5 Luminous flux (Luminaire): 3323 lm Luminous flux (Lamps): 5500 lm Luminaire Wattage: 78.0 W Luminaire classification according to DIN: A40 CIE flux code: 97 99 100 100 61 Fitting: 1 x HIT 70 W (Correction Factor 1.000).

50 Pieces

DIAL 9 Wave, 1 T16 54W, EVG Article No.: 9 Luminous flux (Luminaire): 3256 lm Luminous flux (Lamps): 4650 lm Luminaire Wattage: 56.0 W Luminaire classification according to DIN: E63 CIE flux code: 73 95 99 06 70 Fitting: 1 x T16 54W (Correction Factor 1.000).

Values in Lux, Scale 1:210

[%]

No.

12 Pieces

345251

² = 5.91 W/m ²/100 lx (Ground area: 430.71 m

²)

Total:


Lobby and retail


lighting appraisal


floorplans AM Y

TOILETS CAFE LOUNGE UP

X CAR PARK ACCESS LIFT

RESTAURANT

GAMING

EXTERNAL LOBBY LOBBY

VOID

UP TO GAMING

UP

UP

UP TO RESTAURANT 2 LEVEL

RECEPTION + DIRECTORY

CIRCULATION

DN

GOODS CAR PARK ACCESS LIFT

LEVEL 1: RESTAURANT + GRAMING 1:100

GROUND PLAN: LOBBY + CAFETERIA + TOILETS 1:100

Y’

On the day it favors naturally in the double height that has the ceiling and openings which already allows the passage of natural light to fill light the open lobby and loft located on the middle level, therefore, the first level receives light through the windows and double glass facade that allows a great passage of natural light and space makes this a brightly lit space.

pm Y

TOILETS CAFE LOUNGE UP

X CAR PARK ACCESS LIFT

RESTAURANT

EXTERNAL LOBBY LOBBY

VOID

UP TO GAMING

UP

UP TO RESTAURANT 2 LEVEL

UP

RECEPTION + DIRECTORY

CIRCULATION

DN

GOODS CAR PARK ACCESS LIFT

GROUND PLAN: LOBBY + CAFETERIA + TOILETS 1:100

LEVEL 1: RESTAURANT + GRAMING 1:100

Y’

At night the lighting is artificial, we have a system of LED lights that have the minimum requerimentos to illuminate the area, the LED system is one of the best sources of artificial lighting currently as it has lots of lux (LED Downlight CCT: 3000K) which is perfect for illuminating the quality of life is greater than an incandescent or fluorescent light and the amount of light that emerges is higher than any thus the cost is lower and the light is a saver system. This system is conseiderado be in the structure forming the main steel roof, as each vertex of the geometry is thought to insert a line of LED light, instead of using individual spotlights for space.

GAMING


analyticaldiagrams light paths Y

TOILETS CAFE LOUNGE UP

X

CAR PARK ACCESS LIFT

RESTAURANT

GAMING

EXTERNAL LOBBY LOBBY

VOID

UP TO GAMING

UP

UP

UP TO RESTAURANT 2 LEVEL

RECEPTION + DIRECTORY

CIRCULATION

DN

GOODS CAR PARK ACCESS LIFT

LEVEL 1: RESTAURANT + GRAMING 1:100

GROUND PLAN: LOBBY + CAFETERIA + TOILETS 1:100

Y’

light quality and intensity Y

TOILETS CAFE LOUNGE UP

X

CAR PARK ACCESS LIFT

RESTAURANT

EXTERNAL LOBBY LOBBY

VOID

UP TO GAMING

UP

UP

UP TO RESTAURANT 2 LEVEL

RECEPTION + DIRECTORY

CIRCULATION

DN

GOODS CAR PARK ACCESS LIFT

LEVEL 1: RESTAURANT + GRAMING 1:100

GROUND PLAN: LOBBY + CAFETERIA + TOILETS 1:100

Y’

Cold Lighting

Warm Lighting High

Low

GAMING


secTIONS SUMMER

WINTER

SECTION 1 X-X’ 1:100

DAYLIGHT SUMMER DAYLIGHT WINTER ARTIFICIAL LIGHTING LIGHTING PATHS

LIGHT SHELVES • Enhance room X’ illuminances at the rear of a room • Efficient solar protection in summer for north facades • High ceilings required • Illuminances reduced when sky is overcast

Steel Ceiling Skylights

External shading devices : Louvres Double skin clear glazing

Polished concret floor

Structural concrete columns

SECTION 2 Y-Y’ 1:50


SUMMER

WINTER

SECTION 1 X-X’ 1:100

DAYLIGHT SUMMER DAYLIGHT WINTER ARTIFICIAL LIGHTING LIGHTING PATHS

Steel Ceiling Skylights

External shading devices : Louvres

00 C

D

Double skin clear glazing

CD

Polished concret floor

1000

SPIL

L LG

HT 2

NADIR 2000 CD

Structural concrete columns

SECTION 2 Y-Y’ 1:50

THE BEAM ANGLE DEFINIED WHERE CANDELPOWER IS 50%


lightingsources PHOTOGRAPHY

KIND OF LIGHTING

FEATURES

LED

LED

A light-emitting diode (LED) is a two-lead semiconductor light source. It is a pn-junction diode, which emits light when activated. When a suitable voltage is applied to the leads, electrons are able to recombine with electron holes within the device, releasing energy in the form of photons. This effect is called electroluminescence, and the color of the light (corresponding to the energy of the photon) is determined by the energy band gap of the semiconductor.

According to the Australian Lighting Standards, the external corridor have the escencial light (40 - 160 lux) required ilumination for the waiting room, but in the day we need to use artificial light insted using just natural because the natural light do not penetrate completely this space Reference: AS/NZS 16801680.1 Part 1: General principles and recommendations

A revised downlight specification has been developed for this report, and is outlined in Table 5 (see right‐hand columns). It effectively updates the current DSF downlight specification to take into account the recent emergence of sophisticated test methods for LEDs and the introduction of MEPS for reflector CFLs. The table also lists the key requirements of other LED specification programs for comparison. Proof of certification by these other programs may reduce compliance costs, particularly where program requirements are at least as stringent as those required by IPART. Note that the IEA initiative does not currently include a certification aspect. Downlight LED: Minium Efficacy: 42 lm / w Minium inicial flux: 345 lm (Recomended : 500 lm) Apperture: 16.5

LED Line CCT : 3000K

BENEFITS 1. Long Life Long life time stands out as the number one benefit of LED lights. LED bulbs and diodes have an outstanding operational life time expectation of up to 100.000 hours. This is 11 years of continuous operation, or 22 years of 50% operation. If you leave on the LED fixture for 8h per day it would take around 20 years before you’d have to replace the LED bulb. LED’s are different to standard lighting: They don’t really burn out and stop working like a standard light, moreover the lighting diodes emit lower output levels over a very long period of time and become less bright. 2. Energy Efficiency Todays most efficient way of illumination and lighting, with an estimated energy efficiency of 80%-90% when compared to traditional lighting and conventional light bulbs. This means that about 80% of the electrical energy is converted to light, while a ca. 20% is lost and converted into other forms of energy such as heat. With traditional incandescent light bulbs who operate at 20% energy efficiency only, a 80% of the electricity is lost as heat. Imagine the following scenario: If you use traditional lighting and have an electricity bill of e.g US$ 100, then US$ 80 of that money has been used to heat the room, not to light it! Using LED illumination with 80% efficiency, the electricity costs would be around US$ 20 and you’d have saved around US$ 80. The long operational life time acts as a multiplicator and helps achieve even more energy efficiency, especially large scale and when thinking in terms of urban infrastructure projects, such as cities, railroads and airports. Think of e.g an airport using energy efficient LED lighting exclusively and achieving a 30% power consumption reduction in comparison with an airport using conventional lighting technology. Because the long life span of LED lights, also the maintenance work - think of all the work and energy it would take to purchase, stock and change the conventional light bulbs of an airport you’ll see that you can make significant energy savings also when it comes to maintenance and replacement due to the long operational life times of LED lighting. 3. Ecologically Friendly LED lights are free of toxic chemicals. Most conventional fluorescent lighting bulbs contain a multitude of materials like e.g mercury that are dangerous for the environment. LED lights contain no toxic materials and are 100% recyclable, and will help you to reduce your carbon footprint by up to a third. The long operational life time span mentioned above means also that one LED light bulb can save material and production of 25 incandescent light bulbs. A big step towards a greener future! 4. Durable Quality LEDs are extremely durable and built with sturdy components that are highly rugged and can withstand even the roughest conditions. Because LED lights are resistant to shock, vibrations and external impacts, they make great outdoor lighting systems for rough conditions and exposure to weather, wind, rain or even external vandalism, traffic related public exposure and construction or manufacturing sites. 5. Zero UV Emissions LED illumination produces little infrared light and close to no UV emissions. Because of this, LED lighting is highly suitable not only for goods and materials that are sensitive to heat due to the benefit of little radiated heat emission, but also for illumination of UV sensitive objects or materials such a in museums, art galleries, archeological sites etc. 6. Design Flexibility LEDs can be combined in any shape to produce highly efficient illumination. Individual LEDs can be dimmed, resulting in a dynamic control of light, color and distribution. Well-designed LED illumination systems can achieve fantastic lighting effects, not only for the eye but also for the mood and the mind: LED mood illumination is already being used in airplanes, classrooms and many more locations and we can expect to see a lot more LED mood illumination in our daily lives within the next few years. 7. Operational in Extremely Cold or Hot Temperatures LED are ideal for operation under cold and low outdoor temperature settings. For fluorescent lamps, low temperatures may affect operation and present a challenge, but LED illumination operates well also in cold settings, such as for outdoor winter settings, freezer rooms etc. 8. Light Dispersement LED is designed to focus its light and can be directed to a specific location without the use of an external reflector, achieving a higher application efficiency than conventional lighting. Well-designed LED illumination systems are able to deliver light more efficiently to the desired location. 9. Instant Lighting & Frequent Switching LED lights brighten up immediately and when powered on, which has great advantages for infrastructure projects such as e.g traffic and signal lights. Also, LED lights can switched off and on frequently and without affecting the LED’s lifetime or light emission. In contrast, traditional lighting may take several seconds to reach full brightness, and frequent on/off switching does drastically reduce operational life expectancy. 10. Low-Voltage A low-voltage power supply is sufficient for LED illumination. This makes it easy to use LED lighting also in outdoor settings, by connecting an external solar-energy source and is a big advantage when it comes to using LED technology in remote or rural areas.


graphicanalysis

FALSE COULOUR 3d RENDER

Room 1 / Luminaires (layout plan)

Scale 1 : 210 Luminaire Parts List No.

Pieces

1 2 3

12 20 23

Designation DIAL 17 1 HIT 35W DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ DIAL 5 Aufbaustrahler


diagramanalysis Room 1 / Summary

Height of Room: 5.000 m, Maintenance factor: 0.80 Surface

Project 1 / Luminaire parts list

E av [lx]

E min [lx]

E max [lx]

u0

Workplane

/

261

63

1465

0.243

Floor Ceilings (3)

27 80

248 615

66 108

1610 2992

0.265 /

Walls (6)

38

221

68

14016

/

Workplane: Height: 0.750 m Grid: 128 x 128 Points Boundary Zone: 0.500 m Illuminance Quotient (according to LG7): Walls / Working Plane:

- , Ceiling / Working Plane:

-.

Luminaire Parts List Pieces

1

12

2

20

3 4

23 50

Designation (Correction Factor)

(Luminaire) [lm]

(Lamps) [lm]

P [W]

2036

3400

42.0

4078

5500

78.0

3323 3256

5500 4650

78.0 56.0

509800

6658.0

DIAL 17 1 HIT 35W (1.000) DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ (1.000) DIAL 5 Aufbaustrahler (1.000) DIAL 9 Wave, 1 T16 54W, EVG (1.000) Total:

Specific connected load: 15.46 W/m

DIAL 17 1 HIT 35W Article No.: 17 Luminous flux (Luminaire): 2036 lm Luminous flux (Lamps): 3400 lm Luminaire Wattage: 42.0 W Luminaire classification according to DIN: E10 CIE flux code: 00 00 00 00 60 Fitting: 1 x HIT 35W (Correction Factor 1.000).

20 Pieces

DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ Article No.: 22 Luminous flux (Luminaire): 4078 lm Luminous flux (Lamps): 5500 lm Luminaire Wattage: 78.0 W Luminaire classification according to DIN: E13 CIE flux code: 00 00 12 00 74 Fitting: 1 x HIT -DE 70W (Correction Factor 1.000).

23 Pieces

DIAL 5 Aufbaustrahler Article No.: 5 Luminous flux (Luminaire): 3323 lm Luminous flux (Lamps): 5500 lm Luminaire Wattage: 78.0 W Luminaire classification according to DIN: A40 CIE flux code: 97 99 100 100 61 Fitting: 1 x HIT 70 W (Correction Factor 1.000).

50 Pieces

DIAL 9 Wave, 1 T16 54W, EVG Article No.: 9 Luminous flux (Luminaire): 3256 lm Luminous flux (Lamps): 4650 lm Luminaire Wattage: 56.0 W Luminaire classification according to DIN: E63 CIE flux code: 73 95 99 06 70 Fitting: 1 x T16 54W (Correction Factor 1.000).

Values in Lux, Scale 1:210

[%]

No.

12 Pieces

345251

² = 5.91 W/m ²/100 lx (Ground area: 430.71 m

²)

Total:


renders


acoustic appraisal


floorplans The reverberation time of the retail is expected to be higher then the other spaces. This is due to the open aired and non-absorbant materiality asociated with these spaces. However with added internal aborbive panels, ceiling tiles and baffles. This space is performing reasonably well within the frequencies of music.

ACOUSTIC GOALS - To ensure the exterior traffic noise does not become an issue for the large lobby space - Ensure that the internal areas are performing well in regard to speech intelligibility

Y

Neoprene Noise Absorbant Pads TOILETS CAFE LOUNGE UP

X’ CAR PARK ACCESS LIFT

X

EXTERNAL LOBBY LOBBY

VOID

UP TO GAMING

UP

UP TO RESTAURANT 2 LEVEL

UP

RECEPTION + DIRECTORY

CIRCULATION

DN

GOODS CAR PARK ACCESS LIFT

GROUND PLAN: LOBBY + CAFETERIA + TOILETS 1:100

60dBA medium traffic noise 15m from source

If the SPL drops from 75dBA to 60dBA over 15 metres. Therefore to maximise the use of the open plan within the lobby, a masking speasker system can make this traffic noise unoticable. If the masking speakers are producing a mask at 75dBA then the exterior traffic noise (which is the main acoustic concern of this design) will not be an issue.

75dBA medium traffic noise 1m from source

BOUTIQUE STORES

LEVEL 1: RESTAURANT + GRAMING 1:100

RETAIL


secTIONS Acoustic Concept The retail and lobby areas have vastly different acoustic requirements than the other spaces also. These spaces focus on brining the outside in as through the lower circulation path cut through the building and also the overhead mezzanine levels dealing with retail. As these design decisions take priority over the idealistic low background sound level, realistic acoustic goals must be set. As the street façade is dealing with traffic noise set at 78dBA the internal SPL of the Lobby will be set at 50dBA as set by the ASN2107 recommended for a shopping Centre. Speech intelligibility is going to be an issue at certain points especially with the use of the open plan and mezzanine levels therefore suspended ceiling tiles are implemented to keep it relatively low <1.8, but still performing in the music frequency. Rw + C = 28 (High Frequency) R.T. <1.8 This reverberation time will be achieved through the application of soft surfaces where possible. As there is a double height ceiling in play with the mezzanine level, ceiling tiles must suspended to absorb sound from the lower levels and prevent echoes. Acoustically treated glass which incorporates a PVB (polyvinylbutyral) in order to reduce sound transmission from the external street façade. Acoustic absorption panels will be incorporated where possible on the internal lower level to decrease the reverberation time in spaces required such as specific lobby moments.

MASKING SPEAKER SYSTEM DIRECT SOUND ABSORBED SOUND Suspended tiled ceiling

Free hanging Baffle

Internal Masking speaker

SECTION 2 Y-Y’ 1:50

Double Sliding Door - Acoustic Glass (Viridian VLam Hush)

Double Sliding Door - Acoustic Glass (Viridian VLam Hush)


DETAILS Masking speaker system - covers street level sound in peak traffic times.

Hanging acoustic baffles aiding in sound absorbtion

*Acoustic wall panelling - reduce reverberation

The Lobby and retail space is a very passive lower space of the building. The Lobby in particular is double height allowing for an excellent access route from and too both sides of Argyle street. The Lobby will feel open ended and transparent as it becomes very much a public space. It will need to perform as a balanced and ambient space in order to set the business tone of the internal environment. The lobby will have different acoustic requirements then that of the retail sections which exist on the mezzanine levels. The retail requires a much softer noise level as it requires greater speech intelligibility where it exists to the side of the lobby public space. Within both these spaces there is a large opportunity for exterior street level sounds to become intrusive on the internal environment. Traffic is a major intrusive sound especially being so close to the source. The traffic noise will unfortunately be audible in this space as the passive ventilation and circulation takes priority, however steps are put in place to ensure this is as low as possible. In order to combat these intrusive sounds the lobby exterior is double glazed fixed frame glass in areas exposed to the most peak traffic noise, the interior is also fitted with suspended acoustically tiled ceiling to absorb as much internal sound as possible. The double height space of the lobby is also an issue for speech intelligibility therefore ceiling baffles are utilised and an internal masking speaker system set to mask the intrusive exterior traffic noise is set in place.


thermal appraisal


floorplans Y

TOILETS CAFE LOUNGE UP

X’ CAR PARK ACCESS LIFT

X

EXTERNAL LOBBY LOBBY

VOID

UP TO GAMING

UP

UP TO RESTAURANT 2 LEVEL

UP

RECEPTION + DIRECTORY

CIRCULATION

DN

GOODS CAR PARK ACCESS LIFT

GROUND PLAN: LOBBY + CAFETERIA + TOILETS 1:100

RESTAURANT

LEVEL 1: RESTAURANT + GRAMING 1:100

Y’

GAMING


secTIONS

SECTION 1 X-Xâ&#x20AC;&#x2122; 1:100

With the use of the double layered ceiling, the heat is allowed to escape through the top but also offers moments of shading from the harsh Summer Sun. Louvres in the building will shade low/glaring sunlight into the Lobby and Retail spaces. This is important as direct daylight can often be annoying in retail spaces. The thermal insulation in this space is moderate due to the use of lightweight building materials and many windows. With the use of floor and wall insulation mixed with underfloor cooling and return through the ceiling void should keep the air quite temperate. However, due to the lack of thermal mass in this section and the many windows, there will be much thermal loss. This means that conditioned air will be essential but not always necessary; thanks to the operable windows and the thoroughfare void that will circulate and attract cool air in the summer. Underfloor heating can be activated in the winter.

Summer Sun

Winter Sun

SECTION 2 Y-Yâ&#x20AC;&#x2122; 1:50

Chiller / Boiler


DETAILS

- Underfloor cooling is implemented throughout the whole building design. The Chiller cools the air and pumps it under the raised floor. The raised floor also acts as a thermal barrier between the exposed concrete slab and the floorboards. Insulation between the floorboards and the concrete also helps stop the thermal bridging. - Warm air is returned through the ceiling void and is sent back down to the chiller to be re-chilled and circulated. In Winter; the air is boiled for underfloor heating and the cold air is sucked up through the vents.

- The solar panels help provide electricity to the cost of lighting the building. Winter sunlight ha mised whilst reducing the amount of direct sum plate is exposed to. - Fixed desks are set back to avoid glare but mix open plan space is malleable for those wanting

Stack Effect

Stack Effect

mmer Sun

nter Sun

Winter The Lobby uses the Stack Effect as the Louvres and Windows are closed during the winter and the hot air rises, warming the interior and the cooler air gets returned to the boiler. Underfloor heating and return cooling is also implemented on both floors.

Summer The Lobby uses the Stack Effect to also cool the interior as the windows and louvres are now opened and allow fresh cool air to circulate and remove excess heat near the roof. This along with the underfloor cooling and return heat makes it an economical solution.


a typical office floor


lighting appraisal


floorplans AM

pm


analyticaldiagrams light paths

light quality and intensity

Cold Lighting

Warm Lighting High

Low


sections SUMMER

WINTER

SECTION 1 Y-Y’ 1:50

DAYLIGHT SUMMER DAYLIGHT WINTER ARTIFICIAL LIGHTING LIGHTING PATHS


SUMMER

WINTER

SECTION 1 Y-Y’ 1:50

DAYLIGHT SUMMER DAYLIGHT WINTER ARTIFICIAL LIGHTING LIGHTING PATHS


lightingsources PHOTOGRAPHY

KIND OF LIGHTING

FEATURES

LED

LED

A light-emitting diode (LED) is a two-lead semiconductor light source. It is a pn-junction diode, which emits light when activated. When a suitable voltage is applied to the leads, electrons are able to recombine with electron holes within the device, releasing energy in the form of photons. This effect is called electroluminescence, and the color of the light (corresponding to the energy of the photon) is determined by the energy band gap of the semiconductor.

According to the Australian Lighting Standards, the external corridor have the escencial light (40 - 160 lux) required ilumination for the waiting room, but in the day we need to use artificial light insted using just natural because the natural light do not penetrate completely this space Reference: AS/NZS 16801680.1 Part 1: General principles and recommendations

A revised downlight specification has been developed for this report, and is outlined in Table 5 (see right‐hand columns). It effectively updates the current DSF downlight specification to take into account the recent emergence of sophisticated test methods for LEDs and the introduction of MEPS for reflector CFLs. The table also lists the key requirements of other LED specification programs for comparison. Proof of certification by these other programs may reduce compliance costs, particularly where program requirements are at least as stringent as those required by IPART. Note that the IEA initiative does not currently include a certification aspect. Downlight LED: Minium Efficacy: 42 lm / w Minium inicial flux: 345 lm (Recomended : 500 lm) Apperture: 16.5

LED Line CCT : 3000K

BENEFITS 1. Long Life Long life time stands out as the number one benefit of LED lights. LED bulbs and diodes have an outstanding operational life time expectation of up to 100.000 hours. This is 11 years of continuous operation, or 22 years of 50% operation. If you leave on the LED fixture for 8h per day it would take around 20 years before you’d have to replace the LED bulb. LED’s are different to standard lighting: They don’t really burn out and stop working like a standard light, moreover the lighting diodes emit lower output levels over a very long period of time and become less bright. 2. Energy Efficiency Todays most efficient way of illumination and lighting, with an estimated energy efficiency of 80%-90% when compared to traditional lighting and conventional light bulbs. This means that about 80% of the electrical energy is converted to light, while a ca. 20% is lost and converted into other forms of energy such as heat. With traditional incandescent light bulbs who operate at 20% energy efficiency only, a 80% of the electricity is lost as heat. Imagine the following scenario: If you use traditional lighting and have an electricity bill of e.g US$ 100, then US$ 80 of that money has been used to heat the room, not to light it! Using LED illumination with 80% efficiency, the electricity costs would be around US$ 20 and you’d have saved around US$ 80. The long operational life time acts as a multiplicator and helps achieve even more energy efficiency, especially large scale and when thinking in terms of urban infrastructure projects, such as cities, railroads and airports. Think of e.g an airport using energy efficient LED lighting exclusively and achieving a 30% power consumption reduction in comparison with an airport using conventional lighting technology. Because the long life span of LED lights, also the maintenance work - think of all the work and energy it would take to purchase, stock and change the conventional light bulbs of an airport you’ll see that you can make significant energy savings also when it comes to maintenance and replacement due to the long operational life times of LED lighting. 3. Ecologically Friendly LED lights are free of toxic chemicals. Most conventional fluorescent lighting bulbs contain a multitude of materials like e.g mercury that are dangerous for the environment. LED lights contain no toxic materials and are 100% recyclable, and will help you to reduce your carbon footprint by up to a third. The long operational life time span mentioned above means also that one LED light bulb can save material and production of 25 incandescent light bulbs. A big step towards a greener future! 4. Durable Quality LEDs are extremely durable and built with sturdy components that are highly rugged and can withstand even the roughest conditions. Because LED lights are resistant to shock, vibrations and external impacts, they make great outdoor lighting systems for rough conditions and exposure to weather, wind, rain or even external vandalism, traffic related public exposure and construction or manufacturing sites. 5. Zero UV Emissions

WALL WASHERS Wallwashing is a popular name for a lighting design technique for illumination of large surfaces. It is mainly used with contemporary architecture; in public cultural buildings, museums and galleries; and in landscape lighting.

According to the Australian Lighting Standards, the offices have the escencial light (320 lux) required ilumination that is mean: moderate ilumination. Reference: AS/NZS 16801680.1 Part 1: General principles and recommendations GE LED Wall Washer provides uniform indirect lighting that draws attention to a large area, and helps to de-emphasize textures while cleaning up blemishes on vertical surfaces and walls. This LWW Series LED system is also available with different optics to enhance architectural designs of other specific applications: Cove Lighting and Wall Grazing. : http://www.gelighting.com/LightingWeb/na/solutions/indoor-lighting/ge-led-wall-washer-lww-series.jsp#sthash.IJu4Vy0Y.dpuf 1. 3 different optics for specific applications: Cove Lighting, Wall Washing, Wall Grazing 2. Field adjustable mounting for precise fixture angle 3. Connect up to 300 fixtures in series Color Temperatures: 2700K, 3000K, 4000K Size: 12.6 inches (320mm) Universal 120-277 VAC input design 12° x 80°, 30° x 80°, and 100° x 100° optics choices

1. Long rated life of 50,000 hours 2. 0-10V Dimmable (as low as 3%) 3. Consistent color with 3 step MacAdam ellipse binning 4. Precise use of light output eliminates socket shadows common when using fluorescent fixtures


graphicanalysis

FALSE COULOUR 3d RENDER

Room 1 / Luminaires (layout plan)

Scale 1 : 210 Luminaire Parts List No.

Pieces

1 2 3

12 20 23

Designation DIAL 17 1 HIT 35W DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ DIAL 5 Aufbaustrahler


diagramanalysis Room 1 / Summary

Height of Room: 5.000 m, Maintenance factor: 0.80 Surface

Project 1 / Luminaire parts list

E av [lx]

E min [lx]

E max [lx]

u0

Workplane

/

261

63

1465

0.243

Floor Ceilings (3)

27 80

248 615

66 108

1610 2992

0.265 /

Walls (6)

38

221

68

14016

/

Workplane: Height: 0.750 m Grid: 128 x 128 Points Boundary Zone: 0.500 m Illuminance Quotient (according to LG7): Walls / Working Plane:

- , Ceiling / Working Plane:

-.

Luminaire Parts List Pieces

1

12

2

20

3 4

23 50

Designation (Correction Factor)

(Luminaire) [lm]

(Lamps) [lm]

P [W]

2036

3400

42.0

4078

5500

78.0

3323 3256

5500 4650

78.0 56.0

509800

6658.0

DIAL 17 1 HIT 35W (1.000) DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ (1.000) DIAL 5 Aufbaustrahler (1.000) DIAL 9 Wave, 1 T16 54W, EVG (1.000) Total:

Specific connected load: 15.46 W/m

DIAL 17 1 HIT 35W Article No.: 17 Luminous flux (Luminaire): 2036 lm Luminous flux (Lamps): 3400 lm Luminaire Wattage: 42.0 W Luminaire classification according to DIN: E10 CIE flux code: 00 00 00 00 60 Fitting: 1 x HIT 35W (Correction Factor 1.000).

20 Pieces

DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ Article No.: 22 Luminous flux (Luminaire): 4078 lm Luminous flux (Lamps): 5500 lm Luminaire Wattage: 78.0 W Luminaire classification according to DIN: E13 CIE flux code: 00 00 12 00 74 Fitting: 1 x HIT -DE 70W (Correction Factor 1.000).

23 Pieces

DIAL 5 Aufbaustrahler Article No.: 5 Luminous flux (Luminaire): 3323 lm Luminous flux (Lamps): 5500 lm Luminaire Wattage: 78.0 W Luminaire classification according to DIN: A40 CIE flux code: 97 99 100 100 61 Fitting: 1 x HIT 70 W (Correction Factor 1.000).

50 Pieces

DIAL 9 Wave, 1 T16 54W, EVG Article No.: 9 Luminous flux (Luminaire): 3256 lm Luminous flux (Lamps): 4650 lm Luminaire Wattage: 56.0 W Luminaire classification according to DIN: E63 CIE flux code: 73 95 99 06 70 Fitting: 1 x T16 54W (Correction Factor 1.000).

Values in Lux, Scale 1:210

[%]

No.

12 Pieces

345251

² = 5.91 W/m ²/100 lx (Ground area: 430.71 m

²)

Total:


acoustic appraisal


floorplans ACOUSTIC GOALS - Lower the sound reverberation in all areas to ensure good speech intelligibility - Ensure that Sound does not flank or trasnmitt into meeting areas from break out space

DIRECT SOUND ABSORBED SOUND

Neoprene Noise Absorbant Pads

Acoustic Glazing

Texona Acoustic Panels

Because of the internal acoustic panelling and ceiling tiles the Meeting Room achieves a very low reverberation time and therefore a very good space for speech intelligibility.

Voided space reduces transmission of exterior SPL into Meeting room *achieve 40dBA


sections Acoustic Concept The office partition of the building with comprise of a low background sound level of ranging from 40dBA to 45dBA to some of the more breakout ‘social’ areas. This responds specifically to the AN2107 acoustic guidelines for office buildings. The meeting room requires a lower SPL of 35dBA and a lower range of R.T. with a focus more on speech intelligibility. This requires the façade to remove an approx. 40dBA of the intruding sound from the external environment for the meeting rooms which are situated on the voids within the tower. Rw + C = 38 (High frequency) R.T. = < .8 In order to achieve this R.T. of less than .8 the finishes within the meeting room must be soft ie. Furniture with sound absorbing properties to be placed in the center, and the walls fixed with convex wall absorption panels in order to effectively spread, diffuse and absorb the sound.

Suspended plasterboard ceiling *with ceiling tiles

Steel Frame Double Glazing Pivoted Windows

Master Baffles

Insulated flexible duct

Elevator Noise

Acoustic Glazing Viridian VLam

65dba Medium exterior Traffic

Texona Wall Acoustic Panels

Acoustic Glazing Viridian VLam Acoustic Sealed Doors

Quiet stud masonary wall

Wooden Floor Panels Neoprene noise absorbant pads

Office break-out - require 45dBA *with closed windows DIRECT SOUND ABSORBED SOUND

Meeting Room - require 40dBA

Hallway50dBA


DETAILS

Passively ventilated/ Service-free room - 45dBA in peak traffic times with louvres open

Meeting Room - 33.8 dBA - Quiet Stud Acoustical wall with rw of 51 - Fixed acoustical glass partition

The office space is designed to feel like an intimate environment acoustically, however will feel large and vast extruding itself on the surrounding viewpoints. The nature of this partition will feel very different to the open-aired bar and retail sections in that it provides a lower SPL for more efficient work with opportunities for communication through its open plan. There is however some sounds that have the potential to be intrusive and distracting to the employees inside. The main perpetrator is the street level traffic noise of Parramatta which will have to be made inaudible from inside the office. The main internal acoustic features employed in the design are the closed off and specific material nature of the meeting rooms. The Acoustic paneling on all interior walls and suspended ceiling tiles overhead office desks to absorb the sound and decrease any chance of echoes within the space. The glazed operable windows will decrease the background sound level within the office space. However for every three floors of the office building there will be a passively ventilated space which is completely service free, for this to perform there will be some noise from the street level however will be barely audible when louvers are closed.

Open Plan - 40dBA - Acoustical wall rw of 51 - Fixed acoustical glass partition


thermal appraisal


floorplans


secTIONS

Solar panels - convert solar energy into electricity via the power cells and are stored in a battery to power overhead lights.

wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwww wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwww

- Underfloor cooling is implemented throughout the whole building design. The Chiller cools the air and pumps it under the raised floor. The raised floor also acts as a thermal barrier between the exposed concrete slab and the floorboards. Insulation between the floorboards and the concrete also helps stop the thermal bridging. - Warm air is returned through the ceiling void and is sent back down to the chiller to be re-chilled and circulated. In Winter; the air is boiled for underfloor heating and the cold air is sucked up through the vents.

- The solar panels help provide electricity to the lighting reducing the cost of lighting the building. Winter sunlight has also been maximised whilst reducing the amount of direct summer sun the floorplate is exposed to. - Fixed desks are set back to avoid glare but mixed use spaces or open plan space is malleable for those wanting more light.

Chiller / Boiler


DETAILS Break-out Zone Natural Cooling and Heating System

Winter Windows and External Louvres are closed to reduce passing breeze. Floor to ceiling height has been reduced to keep the space warmer with appliance and body heat.

2500mm

2900mm

2500mm

2900mm

Cool air is returned through the ceiling void to keep the space warm.

Service Free Rooms SummerCooling and Heating Systems Natural Windows and External Louvres are opened to channel passing breeze. Warm air is returned through the ceiling void to keep the space cool.

Solar panels - convert solar energy into electricity via the power cells and are stored in a battery to power overhead lights.

Winter Office Floors Standard Detail

Standard Office has underfloor heating and the addition of winter sun allows the space to be heated well. This is also controlled via the return system. Solar energy is also captured through the solar panels and the energy stored in a battery to power the lights on each floor.

Summer Standard Office has underfloor cooling and the upper window allows air to pass over the floor without disrupting office work. The fixed window is the bottom and the angle of the solar panel stops the direct summer sun.

wwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwww

- Underfloor cooling is implemented throughout the whole building design. The Chiller cools the air and pumps it under the raised floor. The raised floor also acts as a thermal barrier between the exposed concrete slab and the floorboards. Insulation between the floorboards and the concrete also helps stop the thermal bridging.

- The solar panels help provide electricity to the cost of lighting the building. Winter sunlight has mised whilst reducing the amount of direct sum plate is exposed to. - Fixed desks are set back to avoid glare but mixe


bAR AND GAMING


lighting appraisal


floorplans LOWER BAR & GAMING AM

STORAGE

Outdoor Seating

Services - Bathrooms

Gaming - Non Smoking

Gaming - Smoking

pm STORAGE

Outdoor Seating

Services - Bathrooms

Gaming - Non Smoking

Gaming - Smoking


analyticaldiagrams UPPER BALCONY & ROOFTOP FACADE light paths

light quality and intensity

Upper Open - Aired Bar balcony

Upper Open - Aired Gaming Balcony

Cold Lighting

Warm Lighting

Upper Open - Aired Bar balcony

High

Low

Upper Open - Aired Gaming Balcony


sections SUMMER

Open-Aired Roof Facade

Internal environment noise exits through open-aired facade WINTER

Operable windows Internal Louvres

Double Automatic Door - Acoustic Glass (Viridian VLam Hush)

Neoprene Noise Absorbant pads

BAR WING SECTION

Spring Slab lift mount - avoid flanking to underneath offices


SUMMER

Open-Aired Roof Facade

Internal environment noise exits through open-aired facade WINTER

Operable windows Internal Louvres

Double Automatic Door - Acoustic Glass (Viridian VLam Hush)

Neoprene Noise Absorbant pads

BAR WING SECTION

Spring Slab lift mount - avoid flanking to underneath offices


lightingsources PHOTOGRAPHY

KIND OF LIGHTING

FEATURES

LED

LED

A light-emitting diode (LED) is a two-lead semiconductor light source. It is a pn-junction diode, which emits light when activated. When a suitable voltage is applied to the leads, electrons are able to recombine with electron holes within the device, releasing energy in the form of photons. This effect is called electroluminescence, and the color of the light (corresponding to the energy of the photon) is determined by the energy band gap of the semiconductor.

According to the Australian Lighting Standards, the external corridor have the escencial light (40 - 160 lux) required ilumination for the waiting room, but in the day we need to use artificial light insted using just natural because the natural light do not penetrate completely this space Reference: AS/NZS 16801680.1 Part 1: General principles and recommendations

A revised downlight specification has been developed for this report, and is outlined in Table 5 (see right‐hand columns). It effectively updates the current DSF downlight specification to take into account the recent emergence of sophisticated test methods for LEDs and the introduction of MEPS for reflector CFLs. The table also lists the key requirements of other LED specification programs for comparison. Proof of certification by these other programs may reduce compliance costs, particularly where program requirements are at least as stringent as those required by IPART. Note that the IEA initiative does not currently include a certification aspect. Downlight LED: Minium Efficacy: 42 lm / w Minium inicial flux: 345 lm (Recomended : 500 lm) Apperture: 16.5

LED Line CCT : 3000K

BENEFITS 1. Long Life Long life time stands out as the number one benefit of LED lights. LED bulbs and diodes have an outstanding operational life time expectation of up to 100.000 hours. This is 11 years of continuous operation, or 22 years of 50% operation. If you leave on the LED fixture for 8h per day it would take around 20 years before you’d have to replace the LED bulb. LED’s are different to standard lighting: They don’t really burn out and stop working like a standard light, moreover the lighting diodes emit lower output levels over a very long period of time and become less bright. 2. Energy Efficiency Todays most efficient way of illumination and lighting, with an estimated energy efficiency of 80%-90% when compared to traditional lighting and conventional light bulbs. This means that about 80% of the electrical energy is converted to light, while a ca. 20% is lost and converted into other forms of energy such as heat. With traditional incandescent light bulbs who operate at 20% energy efficiency only, a 80% of the electricity is lost as heat. Imagine the following scenario: If you use traditional lighting and have an electricity bill of e.g US$ 100, then US$ 80 of that money has been used to heat the room, not to light it! Using LED illumination with 80% efficiency, the electricity costs would be around US$ 20 and you’d have saved around US$ 80. The long operational life time acts as a multiplicator and helps achieve even more energy efficiency, especially large scale and when thinking in terms of urban infrastructure projects, such as cities, railroads and airports. Think of e.g an airport using energy efficient LED lighting exclusively and achieving a 30% power consumption reduction in comparison with an airport using conventional lighting technology. Because the long life span of LED lights, also the maintenance work - think of all the work and energy it would take to purchase, stock and change the conventional light bulbs of an airport you’ll see that you can make significant energy savings also when it comes to maintenance and replacement due to the long operational life times of LED lighting. 3. Ecologically Friendly LED lights are free of toxic chemicals. Most conventional fluorescent lighting bulbs contain a multitude of materials like e.g mercury that are dangerous for the environment. LED lights contain no toxic materials and are 100% recyclable, and will help you to reduce your carbon footprint by up to a third. The long operational life time span mentioned above means also that one LED light bulb can save material and production of 25 incandescent light bulbs. A big step towards a greener future! 4. Durable Quality LEDs are extremely durable and built with sturdy components that are highly rugged and can withstand even the roughest conditions. Because LED lights are resistant to shock, vibrations and external impacts, they make great outdoor lighting systems for rough conditions and exposure to weather, wind, rain or even external vandalism, traffic related public exposure and construction or manufacturing sites. 5. Zero UV Emissions

WALL WASHERS Wallwashing is a popular name for a lighting design technique for illumination of large surfaces. It is mainly used with contemporary architecture; in public cultural buildings, museums and galleries; and in landscape lighting.

According to the Australian Lighting Standards, the offices have the escencial light (320 lux) required ilumination that is mean: moderate ilumination. Reference: AS/NZS 16801680.1 Part 1: General principles and recommendations GE LED Wall Washer provides uniform indirect lighting that draws attention to a large area, and helps to de-emphasize textures while cleaning up blemishes on vertical surfaces and walls. This LWW Series LED system is also available with different optics to enhance architectural designs of other specific applications: Cove Lighting and Wall Grazing. : http://www.gelighting.com/LightingWeb/na/solutions/indoor-lighting/ge-led-wall-washer-lww-series.jsp#sthash.IJu4Vy0Y.dpuf 1. 3 different optics for specific applications: Cove Lighting, Wall Washing, Wall Grazing 2. Field adjustable mounting for precise fixture angle 3. Connect up to 300 fixtures in series Color Temperatures: 2700K, 3000K, 4000K Size: 12.6 inches (320mm) Universal 120-277 VAC input design 12° x 80°, 30° x 80°, and 100° x 100° optics choices

1. Long rated life of 50,000 hours 2. 0-10V Dimmable (as low as 3%) 3. Consistent color with 3 step MacAdam ellipse binning 4. Precise use of light output eliminates socket shadows common when using fluorescent fixtures


graphicanalysis

FALSE COULOUR 3d RENDER

Room 1 / Luminaires (layout plan)

Scale 1 : 210 Luminaire Parts List No.

Pieces

1 2 3

12 20 23

Designation DIAL 17 1 HIT 35W DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ DIAL 5 Aufbaustrahler


diagramanalysis Room 1 / Summary

Height of Room: 5.000 m, Maintenance factor: 0.80 Surface

Project 1 / Luminaire parts list

E av [lx]

E min [lx]

E max [lx]

u0

Workplane

/

261

63

1465

0.243

Floor Ceilings (3)

27 80

248 615

66 108

1610 2992

0.265 /

Walls (6)

38

221

68

14016

/

Workplane: Height: 0.750 m Grid: 128 x 128 Points Boundary Zone: 0.500 m Illuminance Quotient (according to LG7): Walls / Working Plane:

- , Ceiling / Working Plane:

-.

Luminaire Parts List Pieces

1

12

2

20

3 4

23 50

Designation (Correction Factor)

(Luminaire) [lm]

(Lamps) [lm]

P [W]

2036

3400

42.0

4078

5500

78.0

3323 3256

5500 4650

78.0 56.0

509800

6658.0

DIAL 17 1 HIT 35W (1.000) DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ (1.000) DIAL 5 Aufbaustrahler (1.000) DIAL 9 Wave, 1 T16 54W, EVG (1.000) Total:

Specific connected load: 15.46 W/m

DIAL 17 1 HIT 35W Article No.: 17 Luminous flux (Luminaire): 2036 lm Luminous flux (Lamps): 3400 lm Luminaire Wattage: 42.0 W Luminaire classification according to DIN: E10 CIE flux code: 00 00 00 00 60 Fitting: 1 x HIT 35W (Correction Factor 1.000).

20 Pieces

DIAL 22 Ambilux -W 1xCDM -TD 70+ZZ Article No.: 22 Luminous flux (Luminaire): 4078 lm Luminous flux (Lamps): 5500 lm Luminaire Wattage: 78.0 W Luminaire classification according to DIN: E13 CIE flux code: 00 00 12 00 74 Fitting: 1 x HIT -DE 70W (Correction Factor 1.000).

23 Pieces

DIAL 5 Aufbaustrahler Article No.: 5 Luminous flux (Luminaire): 3323 lm Luminous flux (Lamps): 5500 lm Luminaire Wattage: 78.0 W Luminaire classification according to DIN: A40 CIE flux code: 97 99 100 100 61 Fitting: 1 x HIT 70 W (Correction Factor 1.000).

50 Pieces

DIAL 9 Wave, 1 T16 54W, EVG Article No.: 9 Luminous flux (Luminaire): 3256 lm Luminous flux (Lamps): 4650 lm Luminaire Wattage: 56.0 W Luminaire classification according to DIN: E63 CIE flux code: 73 95 99 06 70 Fitting: 1 x T16 54W (Correction Factor 1.000).

Values in Lux, Scale 1:210

[%]

No.

12 Pieces

345251

² = 5.91 W/m ²/100 lx (Ground area: 430.71 m

²)

Total:


acoustic appraisal


floorplans LOWER BAR & GAMING

ACOUSTIC GOALS - Lower the sound reverberation in the Bar seating to allow for greater speech intelligibility - Ensure that Sound does not flank from the Uperstairs Bar into the below office areas.

Neoprene Pads Floor Tiles 494m^2 Suspended Plasterboard Ceiling with Acoustic Panelling 200m^2 Windows >4mm 72m^2

STORAGE

Outdoor Seating

Services - Bathrooms

Gaming - Non Smoking

Gaming - Smoking

Acoustic Concept The Bar and Gaming partition of the building will have slightly different properties. The Bar will need a low background sound level of 50dBA whereas the Gaming will need 45dBA. Both areas are focused on speech intelligibility however the Bar will need a lower range in order for close conversations to take place with a musical backdrop. The design decision to make the Bar an open aired environment will require the reduction of the SPL from 78dBA traffic noise from the lower level to 45dBA, therefore: Rw + C = 33 (High frequency) R.T. of the Bar <1.2 R.T. of the Gaming <1.5 This will firstly be achieved in the Bar space through the double height ceiling having suspended acoustic ceiling tiles for sound absorption. The use of soft surfaces to be employed as much as possible. The angled faรงade to deal with the exterior intrusive sounds. Secondly the Gaming poker machine space will employ suspended ceiling tiles and limited windows to reduce glare and noise transmission. Acoustically sealed doors from the bar partition.


UPPER BALCONY & ROOFTOP FACADE

Upper Open - Aired Bar balcony

Upper Open - Aired Gaming Balcony The Bar seating area achieves good speech intelligibility for a bar setting. While it could be improved, this would oppose musical performance within this space.


sections BAR WING SECTION

ACOUSTIC GOALS - Lower the sound reverberation in the Bar seating to allow for greater speech intelligibility - Ensure that Sound does not flank from the Uperstairs Bar into the below office areas. Open-Aired Roof Facade

Internal environment noise exits through open-aired facade

Operable windows Internal Louvres

Acoustic Absorbant Ceiling Tiles

Double Automatic Door - Acoustic Glass (Viridian VLam Hush)

Neoprene Noise Absorbant pads

DIRECT SOUND ABSORBED SOUND

Spring Slab lift mount - avoid sound flanking to underneath offices


DETAILS - When rooftop panels are open, reverberation is lower to allow for greater speech intelligibility

oof Facade - Suspended platerboard ceiling with attached ceiling tiles - Acoustic absorbant wall panells to reduce reverberation to <1.2 for added speech intelligibility

- Spring raised floor to reduce noise transmission to below offices

The Bar and Gaming are two separate spaces within the same floor level, and are performing very differently acoustically. The outdoor bar area is stimulating and a busy environment, it will have moments of intimacy and public circulation allowing for a business to run efficiently. The Gaming however is a much more controlled environment where the passive principles within areas of the bar, lobby or open office space will not apply and will have similar requirements to that of the meeting room space. This aspect of the building deals more with the control of the bar noise to the gaming with less focus on intruding environmental background sounds, merely because of the sheer height of the rooftop. Therefore there are sounds which cross from the bar space which are not wanted within the gaming area. These of course are the SPL of people talking, Kitchen and central open bar area. In order for these sounds to not be intruding within the Gaming area the use of double corridor automatic doors is used in order to lessen the sound transfer between the two areas of the Gaming. In particular the Gaming â&#x20AC;&#x2DC;machineâ&#x20AC;&#x2122; area of which limited external light and sound is inherit with a very low reverberation range.


thermal appraisal


floorplans LOWER BAR & GAMING Key Spaces - Overlayed with heat mapping based on daylight, artificial light and natural ventilation.

STORAGE

Outdoor Seating - Even with the double height ceiling; the ground floor uses windows and natural ventilaiton to reduce internal heat load from bodies.

Services - Bathrooms

Gaming - Non Smoking - Gaming (non-Smoking) Area is going to be using conditioned air as the kind of gaming would be difficult with too much breeze.

Gaming - Smoking - Gaming (Smoking) Area does not have conditioned air and is completely operated by strong ventilated circulation.


UPPER BALCONY & ROOFTOP FACADE

Upper Open - Aired Bar balcony - Well designed “Aired Balconies” with a double height ceiling and automatic, operable windows. to release unwanted heat build up. When the room temperature exceeds 23degC or 50%, the windows open and release build up and circulate air.

Upper Open - Aired Gaming Balcony - Well designed “Aired Balcony” with a double height ceiling and automatic, operable windows. to release unwanted heat build up. The Gaming Balcony however, is always operational with ventilation. In times of rain, louvres will stop MOST water penetration, the rest will flow through courtyard drainage.


secTIONS BAR WING SECTION

Open-Aired Operable Roof Facade

Internal Louvres

Summer Sun

Winter Sun

Double height Rooms allow for heat to escape from the ground floor and in a place where there are alot of people with alot of movement; the heat load would be very high. Whilst there will be some nice afternoon daylight, the night sky and few artificial lights brighten/darken the space. The use of glass panels allow good transmission loss which is great in a bar. Underfloor cooling and return air through the ceiling void is there incase conditioned air is required during hot summers.


DETAILS Winter

Automated Rooftop panels are also closed to allow heat to build up and only opened to reduce humidity and stimulate circulation.

Open-Aired Operable Roof Facade Stack Effect

The Stack effect is the main concept of this design with the double height floor with a mezzanine level.

Windows are closed to allow heat to rise through the space. Underfloor activated.

Heating

is

Summer Sun

Summer

Winter Sun

Windows are opened and cooler air is allowed to enter.

Underfloor activated

cooling

is

Stack Effect

Rooftop panels are opened to remove heat and circulate air when temperature is above 23degC and above 50% humidity.


RENDER


coMfort analysis


before OFFICE

BAR & GAMING

RETAIL & LOBBY


after OFFICE

BAR & GAMING

RETAIL & LOBBY


concluSions reflections


Lighting Conclusion With this proposal we are designing a new system to boost natural lighting and not just use the artificial if you do not have a balance of both, so that the building is highly sustainable and wing functional time for different uses which was designed and each use has its own particular technique, lighting, improving the comfort level and creating a space suitable for such uses.

THERMAl CONCLUSION The newly reformed building has had the adequate changes made to the building to ensure that there would be the least amount of Thermal Load to the building. We’ve allowed for all natural strategies to play the primary role in keeping the internal spaces cool in the summer and warm in the winter. There is a secondary heating/cooling system in place for the whole building as a back-up but we believe through our comfort analysis that this will be only required for a maximum of 3 hours in a day. There are also break out spaces and mixed height levels that utilise a purely natural system and would be great for a building immersed in such a congested part of the city. ACOUSTIC CONCLUSION Acoustically speaking the new Argle Street development generally responds to its immediate environment to lessen the noise transmission into the building. Situated within a busy commercial context, various programs surrounding the building impact upon the way various spaces feel within the building and how they are performing. This especially has an impact where the embedded passive design principles present themselves of which there has been some allowance for an increase in the background SPL of the interior. There is a constant balancing act to design these spaces which are performing both thermally and acoustically, of which material specification has had a large impact on the ‘polishing’ of the building and the differentiation of program within the entire structure.


references bibliography


Standars Australia, “Standars Australia”, 30 sept 2001, viewed 26 March 2015, AS/NZS 1680.2.1:2008, < http://www.google.com.au/url?sa=t&rct=j&q=&esrc=s&source=web&cd=2&ved=0CCsQFjAB&url=http%3A%2F%2Finfostore.saiglobal.com%2Fstore%2FPreviewDoc.aspx%3FsaleItemID%3D1404165&ei=lBoVVYDnIsTUmAXs8oKgDA&usg=AFQjCNGpaI9kLL5UFG9OX_ x4jQDa33Gzrw&bvm=bv.89381419,d.dGY>